General Specifications

NS5/NS8/NS10/NS12/NS15

 

Series NS5-V2 NS8-V2 NS10-V2 NS12-V2 NS15-V2
Rated power supply
voltage
24 VDC
Allowable voltage range 20.4 to 27.6 VDC (24 VDC ± 15%)
Power consumption 15 W max. 25 W max. 45 W max.
Ambient operating
temperature
0 to 50 °C
Note:
The ambient operating temperature is subject to the following restrictions according to the
mounting angle.
Mounting angle of 0 to 30° to the horizontal:
When no Expansion Units are mounted, the operating temperature range is 0 to 45 °C.
When a Video Input Unit or a Controller Link Interface Unit is mounted, the ambient
operating temperature is 0 to 35 °C.
Mounting angle of 30 to 90 ° to the horizontal: Operating temperature range of 0 to 50 °C
155_sp_1_1
Storage temperature -20 to 60 °C *1
Ambient operating
humidity
Humidity 20 to 90%RH
(0 to 40 °C)
No condensation
20 to 60%RH (40 to 50 °C)
Humidity 20 to 90%RH
(0 to 50 °C)
No condensation
However, in an environment
exceeding 40 °C/85%RH,
continuous operation 240 h
20 to 60%RH (40 to 50 °C)
Humidity 20 to 90%RH
(0 to 40 °C)
No condensation
20 to 60%RH (40 to 50 °C)
Operating environment No corrosive gases.
Noise immunity Conforms to IEC61000-4-4, 2 kV (power lines).
Vibration resistance
(during operation)
10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz,
9.8 m/s2 30 min each in X, Y, and Z directions
5 to 8.4 Hz, 3.5 mm single
amplitude, 8.4 to 150 Hz,
9.8 m/s2 10 min times
each in X, Y, and Z directions
Shock resistance
(during operation)
147 m/s2 3 times each in direction of X, Y, and Z
Weight 1.0 kg max. 2.0 kg max. 2.3 kg max. 2.5 kg max. 4.2 kg max.
Degree of protection Front operating panel: IP65 oil-proof type and NEMA4 UL type 4. *2
May not be applicable in locations with long-term exposure to oil.
Ground Ground to 100 Ω or less.
Battery life 5 years (at 25 °C): Replace battery within 5 days after the battery runs low (indicator lights
orange).
Applicable standards Certified for conformance to UL 508, UL 1604, EMC Directive, NK, and LR Standards.